Condition and Inspection Report

5 MVA, 33/11 kV power transformer — listing XL-26-0501 (illustrative)

Exchange
Equipment Exchange
Prepared for
Sample Energy Ventures Pvt Ltd (illustrative)
Prepared by
BARREL Digital Exchange desk

1.Item identification

Listing reference
XL-26-0501
Item
Two-winding, core-type, oil-immersed distribution transformer
Serial number
Recorded on the register; shown only on authorised disclosure
OEM / model
Illustrative Transformer Works Ltd, ITW-5000 (illustrative)
Rating
5,000 kVA ONAN, 33/11 kV, vector group Dyn11, 50 Hz
Tap changer
Off-circuit, ±5% in 2.5% steps (5 positions)
Year of manufacture
2016

2.Condition grade and service history

The item is graded Used – tested. The grade rests on the seller's service log, the independent test report of 18 September 2026 and the photographs on file; it is not a statement that the transformer will perform at any particular level after re-energisation.

Condition grade
Used – tested
Operating hours
Approx. 61,000 h between 2017 and April 2026 (seller's log)
Last service
Removed from a 33/11 kV substation in April 2026 after a feeder reconfiguration (seller's declaration)
Oil
Mineral oil, approx. 3,900 litres; last filtered June 2026 (seller's declaration)
Known repairs
None declared by the seller

3.Visual inspection findings

ItemObservationFinding
Tank and weldsNo leaks; surface rust on base channelsObserve
HV and LV bushingsPorcelain intact, no cracks; HV bushing oil levels visiblePass
Radiators and valvesAll 8 radiators fitted; one valve handle missingObserve
Conservator and breatherSilica gel partly pink; replace before energisingObserve
GasketsLight weep at LV turret flange, no dripObserve
Nameplate and markingsLegible; matches declared rating and vector groupPass
Paint and corrosionApprox. 20% surface rust, no pittingObserve
Marshalling box and wiringDry, terminals labelled, glands intactPass

4.Electrical test results

Tests were carried out by an independent test agency on 18 September 2026 at the seller's yard, oil temperature 32 °C, and are reproduced from its report. BARREL did not witness the tests.

TestConditionResultOutcome
Insulation resistance HV–earth5 kV DC, 60 s2,450 MΩPass
Insulation resistance LV–earth2.5 kV DC, 60 s1,650 MΩPass
Insulation resistance HV–LV5 kV DC, 60 s3,100 MΩPass
Polarisation index HV–earth10 min / 1 min1.6Observe
Winding resistance HV, tap 3Per phase, 30 °C1.842 / 1.839 / 1.845 Ω, deviation 0.3%Pass
Winding resistance LVPer phase, 30 °C0.0421 / 0.0419 / 0.0423 Ω, deviation under 1%Pass
Turns ratio, all 5 tapsThree-phase ratio testerWithin 0.2% of nameplate on every tapPass
Magnetising current415 V applied to LV0.18 / 0.17 / 0.18 A, balancedPass
Oil breakdown voltage2.5 mm gap, 6 samplesAverage 58 kVPass
Oil moisture contentLaboratory sample14 ppmPass
Dissolved gas analysis—Not performedNot tested

5.Accessories and storage

Supplied with the item
Off-circuit tap switch, Buchholz relay, oil and winding temperature indicators, magnetic oil gauge, pressure relief device, silica-gel breather, 8 radiators, marshalling box, bi-directional rollers
Not supplied
HV and LV cable boxes, neutral CT, spare bushings
Storage condition
Outdoors on a concrete plinth under a tarpaulin at the seller's yard since April 2026; oil-filled; breather fitted
Packing and freight
Buyer to arrange; approx. 11.5 t gross oil-filled; radiators detachable for transport

6.Warranty, return and inspection terms

Warranty: the seller offers 90 days from delivery against latent defects notified in writing. Transport damage, site faults and consequential loss are excluded. These are the seller's terms and bind the seller, not BARREL.

Return: a return is accepted within 15 days of delivery for a documented nonconformity against this report, with freight for the buyer's account unless agreed otherwise in the purchase order.

Inspection: available by appointment at the seller's yard with three working days' notice. The buyer may appoint its own test agency at its own cost, and the seller will make the item available for a witnessed re-test of the items listed above.

7.Verification record

Trust label
BARREL reviewed
Documents checked
Seller's purchase invoice (2016), asset register extract, independent test report of 18 September 2026, oil test certificate, 24 photographs
Checked on
28 October 2026
What was checked
Consistency between nameplate, invoice and test report; seller's ownership declaration against the documents; photographs match the described item; test values within the ranges usually seen for this class
What was not checked
Tests were not witnessed; no dissolved gas analysis, internal inspection or dismantling; no site survey; no check of the item's suitability for the buyer's application
Prepared by
BARREL Equipment Desk (illustrative)
  • Scope: a desk review of the seller's documents and the independent test agency's report for listing XL-26-0501. The visual findings are taken from the inspection of 18 September 2026 and the photographs on file.
  • Prepared on 03 November 2026 from information current at 28 October 2026. All values are indicative and are not a guarantee of condition, performance, compliance or fitness for a purpose.
  • Not checked: BARREL did not witness the tests; no dissolved gas analysis, internal inspection or site survey was carried out, and the serial number and ownership chain were compared against documents only.
  • This is a sample report for illustration. The company, the item and every figure are fictitious.
  • This is a sample made from made-up data about Sample Energy Ventures Pvt Ltd (illustrative). It shows the layout and depth of the real report; it is not about any real asset, parcel, tender, company or person.